﻿The behaviour of the dimming output at the end of the disabling function can be configured.

*Switch off*: At the end of the disabling function, the dimming output is switched off and enabled again.

*Brightness value*: At the end of disabling, the dimming channel is set to the specified brightness value and released again.

*Memory value*: At the end of disabling, the active and internally saved brightness value prior to switching off last time is set (via the "Switching" or "Central switching" object).

*Tracked brightness value*: At the end of disabling, the status received during the disabling function or the status set before the disabling function is adjusted with the appropriate brightness value. Any time functions still in progress will also be taken into account if necessary.

*No reaction*: At the end of a disabling, the dimming channel shows no reaction and remains in the current set state. Bus control of the dimming channel is enabled again.

*Flashing*: The dimming channel is always enabled again for the bus control at the end of the disabling and flashes on and off. The flashing time is configured generally for all channels on the parameter page "General". During the flashing, the logical switching state is "on 1" and the switch-on brightness is signaled back as brightness. A soft ON/OFF function is ignored during flashing. The flashing status remains active until another bus command is received and specifies another status.